DocumentCode :
1499587
Title :
The FRTU-Based Fault-Zone Isolation Method in the Distribution Systems
Author :
Ko, Yun-Seok ; Kang, Tae-Ku ; Park, Hak-Yeol ; Kim, Ho-Yong ; Nam, Hyo-Seong
Author_Institution :
Dept. of Electron. Eng., Namseoul Univ., Chungnam, South Korea
Volume :
25
Issue :
2
fYear :
2010
fDate :
4/1/2010 12:00:00 AM
Firstpage :
1001
Lastpage :
1009
Abstract :
In this paper, an intelligent feeder remote terminal unit (FRTU)-based operation and control strategy is proposed, which can improve the accuracy and quickness of the fault-zone determination and isolation from such problems as general fault, high impedance fault (HIF) and in-rush current (IRC) in the distribution system, including overhead and underground feeders. In the proposed method, each FRTU inferring the fault or inrush current determines whether its feeder is a fault or not, and whether its sink zone is a fault zone or not, by exchanging fault information (such as current value, voltage value, current direction) with the other FRTUs on the feeders under the ubiquitous-based distribution system that enables the FRTUs to be connected freely to the network. In order to explain the effectiveness of the proposed method, several cases are simulated for typical distribution using the developed simulator.
Keywords :
intelligent control; power distribution control; power distribution faults; FRTU based fault zone isolation method; high impedance fault; in-rush current; intelligent feeder remote terminal unit; overhead feeders; ubiquitous-based distribution system; underground feeders; Distribution system; fault-zone isolation; feeder remote terminal unit (FRTU); ubiquitous system;
fLanguage :
English
Journal_Title :
Power Delivery, IEEE Transactions on
Publisher :
ieee
ISSN :
0885-8977
Type :
jour
DOI :
10.1109/TPWRD.2009.2032051
Filename :
5286298
Link To Document :
بازگشت