Title :
PQ, DQ and CPT control methods for shunt active compensators — A comparative study
Author :
Mortezaei, Ali ; Lute, Christopher ; Godoy Simoes, M. ; Marafao, Fernando P. ; Boglia, Alessandro
Author_Institution :
Electr. Eng. & Comput. Sci., Colorado Sch. of Mines, Golden, CO, USA
Abstract :
This paper investigates three different control techniques for controlling shunt active compensators for harmonic, reactive power and unbalance compensation. The considered methods were the instantaneous real and imaginary power theory (PQ), the Conservative Power Theory (CPT) and the synchronous reference frame method (DQ). So, the major goal is to explore the main similarities and differences in terms of steady state performance, dynamic response and computational complexity of each compensation method. Additionally, the paper also discusses how to achieve selective compensation by means of every technique, by means of suitable power and current decompositions. A three-phase grid with unbalanced non-linear load and non-negligible line impedance was used for comparing the approaches under ideal and deteriorated voltage conditions.
Keywords :
computational complexity; dynamic response; power grids; reactive power control; CPT control; DQ control; PQ control; computational complexity; conservative power theory; current decomposition; dynamic response; harmonic compensation; imaginary power theory; instantaneous real power theory; nonnegligible line impedance; power decomposition; reactive power compensation; shunt active compensator control; steady state performance; synchronous reference frame; three-phase grid; unbalance compensation; unbalanced nonlinear load; Active filters; Control systems; Harmonic analysis; Power harmonic filters; Reactive power; Vectors;
Conference_Titel :
Energy Conversion Congress and Exposition (ECCE), 2014 IEEE
Conference_Location :
Pittsburgh, PA
DOI :
10.1109/ECCE.2014.6953807