Title :
Novel PFC converter suitable for engine-driven generator-interactive three-phase power systems
Author :
Hirachi, K. ; Nakaoka, M.
Author_Institution :
Div. of Res. & Dev., Yuasa Corp., Osaka, Japan
fDate :
3/1/1999 12:00:00 AM
Abstract :
Discontinuous current mode control implementation for three-phase AC-DC converters with active power filtering and power factor correction schemes has attracted special interest in industrial and telecommunication energy systems. This control strategy has practical advantages since it has a simple and cost-effective configuration. However, for emergency engine-driven generators, most three-phase PFC converters with discontinuous current mode control have not been effectively adopted in practice because the conventional PFC circuit configuration has some disadvantages for engine-driven generators connected to three-phase AC mains. A new conceptual PFC converter circuit and system configuration operating with discontinuous current mode control and suitable for engine-driven generators connected to three-phase AC mains is proposed. The operating principle and unique features of the proposed PFC converter is discussed in terms of harmonic currents and PFC converter performance evaluations on the basis of simulation results from two types of conventional three-phase PFC converters
Keywords :
AC-DC power convertors; active filters; electric current control; power factor correction; power harmonic filters; standby generators; active power filtering; control strategy; discontinuous current mode control; emergency engine-driven generators; engine-driven generator; generator-interactive three-phase power systems; harmonic currents; industrial energy systems; operating principle; power factor correction; telecommunication energy systems; three-phase AC mains; three-phase AC-DC converters;
Journal_Title :
Electric Power Applications, IEE Proceedings -
DOI :
10.1049/ip-epa:19990305