Title :
A real-time selective harmonic elimination based on a transient-free, inner closed-loop control for cascaded multilevel inverters
Author :
Hui Zhao ; Tian Jin ; Shuo Wang ; Deliang Wu ; Liang Sun
Author_Institution :
Power Electron. & Electr. Power Res. Lab., Univ. of Texas at San Antonio, San Antonio, TX, USA
Abstract :
Applying the selective harmonic elimination (SHE) technique to grid connected cascaded modular multilevel inverters has been widely discussed in literature. However, due to the difficulties of solving high-order non-linear transcendental equations, the SHE technique cannot be implemented in real time so its applications are limited. This paper presents a technique to convert the non-linear equations to a specific control system and use a look-up table, integral controllers and a decoupling controller to help the system converge to a zero-error steady state. An inner instantaneous observer is introduced to directly extract the harmonic spectrum of the output voltages without directly sensing output voltages. It can not only simplify hardware design but also eliminate the phase delay generated by conventional spectrum extracting algorithm. The proposed technique can achieve an accurate switching angle control and a fast response. Simulation and experimental results verified that the system can achieve zero-error steady state within one line period.
Keywords :
closed loop systems; harmonics suppression; invertors; nonlinear equations; observers; power grids; power system control; power system harmonics; table lookup; SHE technique; decoupling controller; grid connected cascaded modular multilevel inverter; harmonic spectrum extracting algorithm; high-order nonlinear transcendental equation; inner instantaneous observer; integral controller; look-up table; output voltage sensing; phase delay generated elimination; selective harmonic elimination technique; switching angle control; transient-free inner closed-loop control method; zero-error steady state; Equations; Harmonic analysis; Mathematical model; Observers; Steady-state; Switches; cascaded multilevel inverters; instantaneous observer; real time calculation; selective harmonic elimination (SHE); zero-error steady state;
Conference_Titel :
Energy Conversion Congress and Exposition (ECCE), 2014 IEEE
Conference_Location :
Pittsburgh, PA