DocumentCode
1513516
Title
Practical calculation of switching surges at motor terminals
Author
Dick, E.P. ; Gupta, Bineet Kumar ; Pillai, P. ; Narang, A. ; Sharma, D.K.
Author_Institution
Ontario Hydro Res., Toronto, Ont., Canada
Volume
3
Issue
4
fYear
1988
fDate
12/1/1988 12:00:00 AM
Firstpage
864
Lastpage
872
Abstract
Switching of motors results in steep-fronted surges which cause a relatively large turn-to-turn stress in windings. Simplified and detailed methods are presented for calculating the surge level and risetime at the motor terminals for particular configurations. The levels are shown to be strongly affected by shield or conduit grounding practices and are less dependent on motor size or the number of other loads supplied by the metal-clad bus. The risetimes depend mainly on the motor cable impedance, the shield grounding practices, and an equivalent motor capacitance. Less sensitive parameters include metal-clad bus length, the breaker position, and cable losses associated with the dielectric, skin effect, and semiconductive layers. Comparisons are made with surges monitored during normal switching
Keywords
AC motors; surges; switching; breaker position; cable losses; conduit grounding; dielectric layers; equivalent motor capacitance; metal-clad bus length; motor cable impedance; motor terminals; semiconductive layers; shield grounding; skin effect; steep-fronted surges; switching surges; turn-to-turn stress; AC motors; Cable shielding; Capacitance; Grounding; Impedance; Power cables; Samarium; Stress; Surges; Voltage;
fLanguage
English
Journal_Title
Energy Conversion, IEEE Transactions on
Publisher
ieee
ISSN
0885-8969
Type
jour
DOI
10.1109/60.9363
Filename
9363
Link To Document