DocumentCode
151735
Title
Location of shunt faults in radial power distribution systems considering capacitive effect and non-homogeneous lines
Author
Panesso-Hernandez, A. ; Cadena-Zapata, J. ; Mora-Florez, Juan
Author_Institution
Dept. of Electr. Eng., Univ. de La Salle, Bogota, Colombia
fYear
2014
fDate
10-13 Sept. 2014
Firstpage
1
Lastpage
6
Abstract
This article proposes an alternative for low impedance shunt fault location in radial power distribution systems using the fundamentals of voltage and current measured at the power substation. This proposal includes typical characteristics of power distribution systems, such as unbalances, non-homogeneous line sections and untransposed lines; also we consider the capacitive effect that can significantly affect the behavior of a fault location method. The proposed method, presents errors in location of about 1% respect to the radial length where fault is located.
Keywords
electric current measurement; fault location; power distribution; substations; voltage measurement; capacitive effect; current measurement; low impedance shunt fault location; nonhomogeneous line sections; power substation; radial power distribution systems; untransposed lines; voltage measurement; Circuit faults; Fault location; Power distribution; Radio frequency; Resistance; Substations; Voltage measurement; Capacitance; fault location; non-homogeneous lines; power distribution system; unbalance circuits;
fLanguage
English
Publisher
ieee
Conference_Titel
Transmission & Distribution Conference and Exposition - Latin America (PES T&D-LA), 2014 IEEE PES
Conference_Location
Medellin
Print_ISBN
978-1-4799-6250-1
Type
conf
DOI
10.1109/TDC-LA.2014.6955237
Filename
6955237