• DocumentCode
    151735
  • Title

    Location of shunt faults in radial power distribution systems considering capacitive effect and non-homogeneous lines

  • Author

    Panesso-Hernandez, A. ; Cadena-Zapata, J. ; Mora-Florez, Juan

  • Author_Institution
    Dept. of Electr. Eng., Univ. de La Salle, Bogota, Colombia
  • fYear
    2014
  • fDate
    10-13 Sept. 2014
  • Firstpage
    1
  • Lastpage
    6
  • Abstract
    This article proposes an alternative for low impedance shunt fault location in radial power distribution systems using the fundamentals of voltage and current measured at the power substation. This proposal includes typical characteristics of power distribution systems, such as unbalances, non-homogeneous line sections and untransposed lines; also we consider the capacitive effect that can significantly affect the behavior of a fault location method. The proposed method, presents errors in location of about 1% respect to the radial length where fault is located.
  • Keywords
    electric current measurement; fault location; power distribution; substations; voltage measurement; capacitive effect; current measurement; low impedance shunt fault location; nonhomogeneous line sections; power substation; radial power distribution systems; untransposed lines; voltage measurement; Circuit faults; Fault location; Power distribution; Radio frequency; Resistance; Substations; Voltage measurement; Capacitance; fault location; non-homogeneous lines; power distribution system; unbalance circuits;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Transmission & Distribution Conference and Exposition - Latin America (PES T&D-LA), 2014 IEEE PES
  • Conference_Location
    Medellin
  • Print_ISBN
    978-1-4799-6250-1
  • Type

    conf

  • DOI
    10.1109/TDC-LA.2014.6955237
  • Filename
    6955237