DocumentCode :
1519
Title :
Flashover tests on air gap of ??800kV DC transmission line under composite DC and switching impulse voltage
Author :
Yongli Liao ; Ruihai Li ; Chao Gao ; Guoli Wang ; Zhihong Liu
Author_Institution :
Electr. Power Res. Inst., China Southern Power Grid Co., Ltd., Guangzhou, China
Volume :
21
Issue :
5
fYear :
2014
fDate :
Oct. 2014
Firstpage :
2095
Lastpage :
2101
Abstract :
This paper deals with the air gap insulation of ±800 kV DC transmission systems under composite DC and switching impulse voltage. The gaps studied were representative of ±800 kV DC transmission line, as rod-to-plane and conductor-to-tower gaps. The flashover voltages of the gaps at an altitude of 2100 m were determined for a pure switching impulse and composite voltages of DC and switching impulse. It is found that there are clear increase in the composite flashover voltage of both rod-to-plane and conductor-to-tower gaps, compared with those in the gap that only impulse voltage was applied. From the test results, the flashover voltage increases by 17-23%in the rod-to-plane gap and 5-10% in the conductor-to-tower gap, when the DC voltage of 800 kV is pre-stressed. The standard deviations have little obvious variation under the pre-stressed DC voltage and its average value is 4-4.5% in the tests. Additionally, a 1,000,000 fps high speed CCD camera is used to observe the breakdown process for investigation on the influence of pre-stressed DC voltage on the conductor. The leader inception and breakdown process properties were studied. These data and explanation are useful for ±800kV DC insulation design and testing.
Keywords :
DC power transmission; air gaps; flashover; CCD camera; DC transmission line; DC transmission systems; air gap insulation; breakdown process properties; composite DC voltage; composite flashover voltage; conductor-to-tower gaps; distance 2100 m; leader inception; prestressed DC voltage; rod-to-plane gaps; switching impulse voltage; voltage 800 kV; Breakdown voltage; Flashover; Optical switches; Power transmission lines; Standards; ??800 kV DC line; Air gap insulation; composite voltages; high altitude; switching impulse;
fLanguage :
English
Journal_Title :
Dielectrics and Electrical Insulation, IEEE Transactions on
Publisher :
ieee
ISSN :
1070-9878
Type :
jour
DOI :
10.1109/TDEI.2014.004003
Filename :
6927338
Link To Document :
بازگشت