• DocumentCode
    1519198
  • Title

    Interlaboratory comparison of high direct voltage resistor dividers

  • Author

    Li, Yi ; Rungis, Juris ; Kim, Kyu-Tae ; Cho, Yong Myung ; McComb, Terry R. ; Dunn, John G. ; Van der Zwan, Len ; Hoffman, D.

  • Author_Institution
    High Voltage Lab., CSIRO, Lindfield, NSW, Australia
  • Volume
    48
  • Issue
    2
  • fYear
    1999
  • fDate
    4/1/1999 12:00:00 AM
  • Firstpage
    158
  • Lastpage
    161
  • Abstract
    A 150-kV divider from the National Measurements Laboratory of Australia was used as a travelling standard in comparison tests against standard dividers maintained at the Korean Research Institute of Standards and Science and the National Research Council of Canada. Results are presented in terms of the relative ratio changes between these dividers and the transfer standard under high voltages. In addition to establishing the relative agreement in high direct voltage measurements, the comparison tests were shown to be especially valuable for evaluating the ratio drifts of the dividers under prolonged application of high voltage
  • Keywords
    high-voltage techniques; transfer standards; voltage dividers; voltage measurement; 150 kV; high direct voltage measurement; interlaboratory comparison; ratio drift; resistor divider; transfer standard; travelling standard; Australia; Corona; Councils; Electrical resistance measurement; Laboratories; Measurement standards; Resistors; Temperature; Testing; Voltage measurement;
  • fLanguage
    English
  • Journal_Title
    Instrumentation and Measurement, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0018-9456
  • Type

    jour

  • DOI
    10.1109/19.769552
  • Filename
    769552