DocumentCode :
1520109
Title :
Condition monitoring of power transformer on-load tap-changers. II. Detection of ageing from vibration signatures
Author :
Kang, P. ; Birtwhistle, D.
Author_Institution :
United Technol. Res. Center, East Hartford, CT, USA
Volume :
148
Issue :
4
fYear :
2001
fDate :
7/1/2001 12:00:00 AM
Firstpage :
307
Lastpage :
311
Abstract :
The paper describes a technique for online automatic condition assessment of an on-load tap-changer (OLTC) using a self-organising map (SOM). With a condition indicator giving the correct indication of the current condition status, an estimate can be made of the remaining life of the equipment. The condition assessment technique is demonstrated using the signatures collected by online monitoring systems installed on selector type OLTCs in distribution substations. Using the realtime fault detection procedure, reliable identification of incipient faults in the equipment can be achieved for the pre-specified false alarming rate
Keywords :
ageing; computerised monitoring; condition monitoring; fault diagnosis; power engineering computing; power system faults; power transformer testing; self-organising feature maps; vibration measurement; ageing detection; condition indicator; condition monitoring; distribution substations; incipient faults identification; online automatic condition assessment; online monitoring systems; power transformer on-load tap-changers; remaining life estimation; self-organising feature map; vibration signatures;
fLanguage :
English
Journal_Title :
Generation, Transmission and Distribution, IEE Proceedings-
Publisher :
iet
ISSN :
1350-2360
Type :
jour
DOI :
10.1049/ip-gtd:20010388
Filename :
941372
Link To Document :
بازگشت