    Flicker Evaluation of the SeaGen Tidal Power Plant

  • Author

    Thiringer, Torbjorn ; MacEnri, Joe ; Reed, M.

  • Author_Institution
    Chalmers Univ. of Technol., Goteborg, Sweden
  • Volume
    2
  • Issue
    4
  • fYear
    2011
  • Firstpage
    414
  • Lastpage
    422
  • Abstract
    This paper presents the power quality evaluation of a 1.2-MW tidal power plant. The results show that the unit works well and that the power quality impact is moderate to low and for future units which most likely will have more turbines, the power quality impact will be very low. The wind turbine power quality standard IEC 61400-21 was used in this investigation, and was adequate; however, regarding the connecting transients, there could be a need for a specific standard. It is found that the power level is well controlled at higher water speeds; the maximum 10-min power is found to be 1.21 MW. The maximum 2-s value is found to be 1.46 MW and the maximum 60-s value is found to be 1.30 MW. The reactive power exchange with the grid is negligible; at full load, the power factor is 0.99. The flicker coefficient is between 1 and 5, depending on the grid impedance angle. Finally, it can be said that the maximum total harmonic distortion (THD) for the voltages is found to be 1.2% and for the current 0.65% during operation with the complete power plant.
  • Keywords
    power supply quality; tidal power stations; SeaGen tidal power plant; flicker evaluation; grid impedance angle; maximum total harmonic distortion; power 1.2 MW; power factor; power quality evaluation; reactive power exchange; IEC standards; Power generation; Power quality; Reactive power; Tides; Total harmonic distortion; Wind turbines; Flicker emission; power quality; tidal energy;
  • fLanguage
    English
  • Journal_Title
    Sustainable Energy, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    1949-3029
  • Type

    jour

  • DOI
    10.1109/TSTE.2011.2157182
  • Filename
    5771609