DocumentCode :
1522727
Title :
Improving insulator reliability with insulating barriers
Author :
Yamano, Y. ; Takahashi, Y. ; Kobayashi, S.
Author_Institution :
Dept. of Eng., Chiba Univ., Japan
Volume :
25
Issue :
6
fYear :
1990
fDate :
12/1/1990 12:00:00 AM
Firstpage :
1174
Lastpage :
1179
Abstract :
When an insulating barrier is set up on an insulator with an inner electrode, suppression of negative surface leaderlike discharge and increase in AC flashover voltage are observed over a range of barrier distance (the distance between the HV electrode and the barrier) of ≲15 mm (critical value). When the barrier distance is longer than the critical value, a punch-through breakdown of the insulator near the junction of the barrier and the insulating surface sometimes occurs. This punch-through breakdown voltage is much lower than the AC flashover voltage for the insulator without a barrier
Keywords :
flashover; insulators; reliability; surface discharges; AC flashover voltage; HV electrode; barrier distance; breakdown voltage; inner electrode; insulating barriers; insulator reliability; negative surface leaderlike discharge; punch-through breakdown; Agricultural engineering; Cable insulation; Dielectrics and electrical insulation; Electrodes; Flashover; Gas insulation; Insulators; Partial discharges; Surface discharges; Voltage;
fLanguage :
English
Journal_Title :
Electrical Insulation, IEEE Transactions on
Publisher :
ieee
ISSN :
0018-9367
Type :
jour
DOI :
10.1109/14.64505
Filename :
64505
Link To Document :