• DocumentCode
    1524474
  • Title

    Evaluation of jacket materials and configurations and effect of moisture absorbing materials on preventing water tree growth in power cables

  • Author

    Cherukupalli, S.E. ; Colwell, M. ; Valli, Gino

  • Author_Institution
    Powertech Labs., Surrey, Canada
  • Volume
    14
  • Issue
    3
  • fYear
    1999
  • fDate
    7/1/1999 12:00:00 AM
  • Firstpage
    690
  • Lastpage
    698
  • Abstract
    Polymer insulated medium voltage cables have experienced premature failures in-service, due in large part to water treeing. Research has shown that the initiation sites of these water trees are often located where there are stress enhancements at the insulation/semiconducting shield interface and where water soluble contaminants permeate into the insulation. Material suppliers, cable manufacturers and users have introduced improved materials and cable designs as well as processing, manufacturing, transport, storage, and installation techniques that minimize contamination. Despite these advancements, gradual contamination can still occur due to the diffusion of ground water into the insulation. In fact, certain contaminants that are carried through the semiconductor/insulation shield interfaces tend to promote water tree growth. Manufacturers are now beginning to recognise this problem and have suggested the use of moisture resistant cables with jackets made of PVC, polyethylene or metal/polymer laminates along with underjacket water absorbing materials. This paper discusses the effectiveness of different jackets and materials and presents data on the effectiveness of water absorbing materials in delaying water permeation into the insulation. A simple and efficient cable-cell technique was developed which monitored the effectiveness of complete cable designs, by measuring the long-term water permeation resistance of short lengths of distribution class cables
  • Keywords
    cable sheathing; power cable testing; trees (electrical); PVC; cable jacket materials; cable-cell technique; contamination minimisation; distribution class cables; insulation/semiconducting shield interface; long-term water permeation resistance measurement; metal/polymer laminates; moisture absorbing materials; moisture resistant cables; polyethylene; polymer insulated medium voltage cables; power cables; premature failures; stress enhancements; underjacket water absorbing materials; water absorbing materials; water permeation delay; water soluble contaminants; water tree growth prevention; water treeing; Cable insulation; Contamination; Manufacturing processes; Material storage; Plastic insulation; Polymers; Semiconductor device manufacture; Semiconductor materials; Trees - insulation; Water pollution;
  • fLanguage
    English
  • Journal_Title
    Power Delivery, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0885-8977
  • Type

    jour

  • DOI
    10.1109/61.772301
  • Filename
    772301