DocumentCode :
1524579
Title :
A new accurate fault locating algorithm for series compensated lines
Author :
Saha, M.M. ; Izykowski, J. ; Rosolowski, E. ; Kasztenny, B.
Author_Institution :
ABB Network Partner AB, Vasteras, Sweden
Volume :
14
Issue :
3
fYear :
1999
fDate :
7/1/1999 12:00:00 AM
Firstpage :
789
Lastpage :
797
Abstract :
This paper presents a new, accurate and robust fault locating algorithm for series compensated lines. The algorithm is developed as a one-end fundamental frequency based technique and offsets both the series compensation effect and the reactance effect resulting from the remote end in-feed. The method uses phase coordinates (abc) instead of symmetrical components (012). The basic algorithm is presented for a line compensated by one three-phase bank of series capacitors. The presented fault locating method has been extensively tested using the EMTP model of a 400 kV 300 km transmission line. The enclosed results demonstrate very high accuracy and robustness of the algorithm
Keywords :
capacitor storage; compensation; fault location; power transmission faults; power transmission lines; 300 km; 400 kV; EMTP model; fault locating algorithm; fault locating method; one-end fundamental frequency; phase coordinates; reactance effect; remote end in-feed; robust fault locating algorithm; series compensated lines; series compensation effect; three-phase series capacitor bank; transmission line; Capacitors; Circuit faults; Distributed parameter circuits; Fault location; Frequency; IEEE members; Power system relaying; Power transmission lines; Testing; Voltage;
fLanguage :
English
Journal_Title :
Power Delivery, IEEE Transactions on
Publisher :
ieee
ISSN :
0885-8977
Type :
jour
DOI :
10.1109/61.772316
Filename :
772316