DocumentCode :
1524701
Title :
A new method to decrease ground resistances of substation grounding systems in high resistivity regions
Author :
Meng, Qingbo ; He, Jinliang ; Dawalibi, F.P. ; Ma, J.
Author_Institution :
Northeast China Power Bur., Shenyang, China
Volume :
14
Issue :
3
fYear :
1999
fDate :
7/1/1999 12:00:00 AM
Firstpage :
911
Lastpage :
916
Abstract :
Decreasing the ground resistance of a grounding system in high resistivity soil is often a formidable task. A new method is proposed to decrease ground resistances. This method requires three steps: (1) drilling deep holes in the ground; (2) developing cracks in the soil by means of explosions in the holes; and (3) filling the holes with low resistivity materials (LRM) under pressure. Most of the cracks around the vertical conductors will be filled with LRM and a complex network of low resistivity tree-like cracks linked to the substation grid is formed. The principle of decreasing ground resistances using this new method is described and the effectiveness of the new method is examined. Application of this method to power system grounding is presented together with measurement results
Keywords :
cracks; earthing; electric resistance; electrical resistivity; soil; substations; deep holes drilling; explosions; ground resistances decrease; high resistivity regions; holes filling; low resistivity materials; low resistivity tree-like cracks; soil cracks development; substation grid; substation grounding systems; vertical conductors; Complex networks; Conducting materials; Conductivity; Drilling; Explosions; Filling; Grounding; Power system measurements; Soil; Substations;
fLanguage :
English
Journal_Title :
Power Delivery, IEEE Transactions on
Publisher :
ieee
ISSN :
0885-8977
Type :
jour
DOI :
10.1109/61.772333
Filename :
772333
Link To Document :
بازگشت