DocumentCode :
1524843
Title :
Field stringing test near a live conductor at the Hokkaido-Honshu HVDC link line
Author :
Suda, Tomotaka ; Amano, Yuto ; Fujii, Koichiro
Author_Institution :
Central Res. Inst. of Electr. Power Ind., Tokyo, Japan
Volume :
14
Issue :
3
fYear :
1999
fDate :
7/1/1999 12:00:00 AM
Firstpage :
1062
Lastpage :
1068
Abstract :
A ±500 kV HVDC transmission line is being constructed jointly by some electric power companies in Japan. Following construction of this overhead transmission line, the ability to work near a live line in a safe manner is one of the most important factors for system reliability. We conducted a survey of work near a live line using the ±250 kV Hokkaido-Honshu HVDC Link Line in July 1990 before this overhead transmission line was upgraded. As a result, we clarified various problems in the work conducted near a live line and suggested some countermeasures such as the grounding of stringing conductors at more than one point
Keywords :
HVDC power transmission; earthing; overhead line conductors; power overhead lines; safety; 250 kV; 500 kV; Hokkaido-Honshu HVDC link line; Japan; electric power companies; field stringing test; live conductor; overhead transmission line; stringing conductors grounding; Conductors; Current measurement; Dielectrics and electrical insulation; Electric shock; HVDC transmission; Poles and towers; Power transmission lines; Testing; Voltage; Wires;
fLanguage :
English
Journal_Title :
Power Delivery, IEEE Transactions on
Publisher :
ieee
ISSN :
0885-8977
Type :
jour
DOI :
10.1109/61.772354
Filename :
772354
Link To Document :
بازگشت