Title
Factors affecting the commutation reactance of direct connected generator-converter units
Author
Dinh, Q.N. ; Arrillaga, J.
Author_Institution
Dept. of Electr. & Electron. Eng., Canterbury Univ., Christchurch, New Zealand
Volume
14
Issue
3
fYear
1999
fDate
7/1/1999 12:00:00 AM
Firstpage
1090
Lastpage
1095
Abstract
The effect of generator subtransient reactance, rotor saliency, the number of generators in the group connection configuration and adjustable speed operation on the commutation reactance and harmonic levels of direct connected units are examined. Restriction limits for firing angles imposed by the commutation angle, generator terminal power factor, equivalent continuous negative-sequence harmonic loading are derived that permit the use of normal generators in direct connected units without the need for extra harmonic loading capacity. The generator harmonic ratings can be taken at the nominal speed and rated power output
Keywords
AC generators; HVDC power convertors; commutation; electric reactance; power conversion harmonics; power factor; rotors; HVDC converters; adjustable speed operation; commutation angle; commutation reactance; direct connected generator-converter units; direct connected units; equivalent continuous negative-sequence harmonic loading; firing angle restriction limits; generator harmonic ratings; generator subtransient reactance effect; generator terminal power factor; harmonic levels; rotor saliency effect; AC generators; HVDC transmission; Iterative algorithms; Power generation; Power harmonic filters; Power system harmonics; Rotors; Thermal stresses; Torque converters; Voltage control;
fLanguage
English
Journal_Title
Power Delivery, IEEE Transactions on
Publisher
ieee
ISSN
0885-8977
Type
jour
DOI
10.1109/61.772358
Filename
772358
Link To Document