• DocumentCode
    1525075
  • Title

    Investigation of the flashover of a FRP hot stick while in use for live line work at 500 kV

  • Author

    McDermid, W. ; Bromley, J.C. ; Dodds, D.J. ; Swatek, D.R.

  • Author_Institution
    Manitoba Hydro, Winnipeg, Man., Canada
  • Volume
    14
  • Issue
    3
  • fYear
    1999
  • fDate
    7/1/1999 12:00:00 AM
  • Firstpage
    1158
  • Lastpage
    1166
  • Abstract
    In October 1997 Manitoba Hydro experienced the flashover of a FRP hot stick during live line work at 500 kV AC. The paper describes the live line work which was being done, the weather and the condition of the hot stick. A series of tests were made to investigate factors which may have contributed to the flashover. The adequacy of available tests for FRP hot sticks is discussed. The corrective measures which have been taken prior to resuming work of this type are described
  • Keywords
    fibre reinforced composites; flashover; insulation testing; maintenance engineering; power overhead lines; 500 kV; FRP hot stick flashover; Manitoba Hydro; corrective measures; flashover testing; live line working; power overhead line maintenance; Accidents; Conductors; Fasteners; Fiber reinforced plastics; Flashover; Insulation; Optical fiber testing; Poles and towers; Power transmission lines; Voltage;
  • fLanguage
    English
  • Journal_Title
    Power Delivery, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0885-8977
  • Type

    jour

  • DOI
    10.1109/61.772387
  • Filename
    772387