DocumentCode :
1526817
Title :
Protection of unified power quality conditioner against the load side short circuits
Author :
Axente, I. ; Basu, Mainak ; Conlon, Michael F. ; Gaughan, Kevin
Author_Institution :
Sch. of Electr. Eng. Syst., Dublin Inst. of Technol., Dublin, Ireland
Volume :
3
Issue :
4
fYear :
2010
fDate :
7/1/2010 12:00:00 AM
Firstpage :
542
Lastpage :
551
Abstract :
This study presents a protection scheme for protecting the series inverter of a unified power quality conditioner (UPQC). The proposed scheme protects the series inverter from overcurrents and overvoltages, which appear during short-circuit faults on the load side of the UPQC. The main protection element is a crowbar connected across the secondary of the series transformer and consists of a pair of antiparallel connected thyristors, which is governed by a simple Zener diode-based control circuit. In the case of an overvoltage, the crowbar short circuits the secondary of the transformer, thus removing the overvoltage and diverting the fault current from the series inverter. An additional circuit is used to disable the inverters in overcurrent conditions. The effectiveness of the proposed protection scheme is demonstrated both through simulation and experimentation.
Keywords :
Zener diodes; invertors; overcurrent protection; overvoltage protection; power supply quality; power transformers; thyristor applications; Zener diode-based control circuit; antiparallel connected thyristors; fault currents; load side short circuits; overcurrents; overvoltages; protection scheme; series inverter; series transformer; short-circuit faults; unified power quality conditioner protection;
fLanguage :
English
Journal_Title :
Power Electronics, IET
Publisher :
iet
ISSN :
1755-4535
Type :
jour
DOI :
10.1049/iet-pel.2009.0111
Filename :
5497961
Link To Document :
بازگشت