Title :
Multivariate Analysis of Transformer Resonant Overvoltages in Power Stations
Author :
Gustavsen, Bjørn ; Brede, Arne Petter ; Tande, John Olav
Author_Institution :
SINTEF Energy Res., Trondheim, Norway
Abstract :
In this paper, cable-transformer resonant overvoltages are studied on the low-voltage (LV) side of a 410-MVA generator step-up (main) transformer, due to ground fault and energization. The transformer is placed in a network configuration often found in Norwegian hydropower stations. The overvoltages are calculated when systematically varying the length of the high-voltage (HV) side cable and that of the cable between the main transformer LV side and the station transformer. This multivariate analysis is performed efficiently, using frequency-domain calculations and the inverse Numerical Laplace Transform. Time-domain simulations are used for analyzing the critical cases in detail. Both types of calculations make use of a blackbox, wideband model of the transformer, and novel procedures are introduced for initializing computations from correct 50-Hz initial conditions. Among the findings are that extreme overvoltages can occur on the station transformer if current-limiting reactors are placed in series with the cable between the main transformer LV side and the station transformer.
Keywords :
Laplace transforms; current limiting reactors; overvoltage; power transformer protection; cable-transformer resonant overvoltages; current-limiting reactors; energization; frequency-domain calculations; generator step-up transformer; ground fault; inverse numerical Laplace transform; low-voltage side; multivariate analysis; power stations; station transformer; time-domain simulations; Current limiters; Hydroelectric power generation; Power cables; Power generation; Power transformer insulation; Resonance; Transient analysis; Cable; overvoltage; power station; resonance; transformer;
Journal_Title :
Power Delivery, IEEE Transactions on
DOI :
10.1109/TPWRD.2011.2143436