DocumentCode :
1528779
Title :
Transient Earth Voltage Measurement in PD Detection of Artificial Defect Models in \\hbox {SF}_{6}
Author :
Ren, Ming ; Dong, Ming ; Ren, Zhong ; Peng, Hua-Dong ; Qiu, Ai-Ci
Author_Institution :
State Key Lab. of Electr. Insulation for Power Equip., Xi´´an Jiaotong Univ., Xi´´an, China
Volume :
40
Issue :
8
fYear :
2012
Firstpage :
2002
Lastpage :
2008
Abstract :
This paper mainly discussed the utilization of transient Earth voltage measurement (TEVM) in partial discharge (PD) detection of gas insulation switchgear. Four typical artificial defect models in SF6 such as spikes fixed on high voltage (HV) conductor, suspended metals, voids in dielectric, and metal particles on the surface of dielectric had been used as test objects in ac PD experiments with the aid of the synchronized PD signals sampled from a transient Earth voltage sensor, photomultiplier, Rogowski monitor, and PDCheck system. The measuring results of TEVM results, which included the phase distribution of PD, the relative amplitude, and the pulse number of different voltage thresholds, showed good consistency with three other methods and had better sensitivity of detection in spark or corona PD patterns. For further study, the frequency distributions of the three PD patterns were analyzed and discussed for understanding the different measurement sensitivities showed in different typical defects in SF6 . In addition, TEVM was applied to detect PD under oscillating impulse voltage. As an example, the needle-plane electrode with short gap was adopted under 613.2-kHz oscillating impulse, which showed the effectiveness in this kind of detection.
Keywords :
SF6 insulation; corona; electric sensing devices; gas insulated switchgear; partial discharge measurement; photomultipliers; sparks; transients; PD detection; PDCheck system; Rogowski monitor; SF6; TEVM; artificial defect model; corona PD pattern; frequency distribution; gas insulation switchgear; oscillating impulse voltage; partial discharge; phase distribution; photomultiplier; pulse number; relative amplitude; spark PD pattern; synchronized PD signal; transient Earth voltage sensor; transient earth voltage measurement; voltage threshold; Discharges; Metals; Needles; Partial discharges; Sulfur hexafluoride; Voltage measurement; Gas insulation switchgear (GIS); insulation defect; insulation diagnosis; partial discharge (PD); transient Earth voltage measurement (TEVM);
fLanguage :
English
Journal_Title :
Plasma Science, IEEE Transactions on
Publisher :
ieee
ISSN :
0093-3813
Type :
jour
DOI :
10.1109/TPS.2012.2199135
Filename :
6209438
Link To Document :