DocumentCode :
1531762
Title :
Investigation of alternative residual current compensation for improving series compensated line distance protection
Author :
Ghassemi, F. ; Johns, A.T.
Author_Institution :
City Univ., London, UK
Volume :
5
Issue :
2
fYear :
1990
fDate :
4/1/1990 12:00:00 AM
Firstpage :
567
Lastpage :
574
Abstract :
The effect of the residual compensation factor on the measuring accuracy of distance protection measurements when an earth fault occurs on a series compensated line is investigated. It is shown that, when conventional residual compensation is used, there will be an error in the impedance measurement which depends on the ratio Isa (Isa+KcIres ) where Isa is the faulted phase current at the relaying point, Kc is the conventional residual compensation factor, and Ires is the residual current. It is also shown that this expression depends on load current and source conditions at the line ends. In consequence, errors of measurement and concomitant overreaching/underreaching can occur when conventional residual compensation methods, as applied to plain feeders, are used in series compensated applications. An alternative method of compensation has therefore been developed. This has been found to improve accuracy of measurement at the boundary and relay measurement integrity for other fault positions in series compensated line applications
Keywords :
compensation; power system protection; alternative residual current compensation; earth fault; load current; relay measurement integrity; series compensated line distance protection; Capacitors; Circuit faults; Impedance measurement; Instruction sets; Power generation economics; Power system economics; Protection; Protective relaying; Relays; Voltage;
fLanguage :
English
Journal_Title :
Power Delivery, IEEE Transactions on
Publisher :
ieee
ISSN :
0885-8977
Type :
jour
DOI :
10.1109/61.53058
Filename :
53058
Link To Document :
بازگشت