DocumentCode :
1532306
Title :
Separation of core losses in distribution transformers using experimental methods
Author :
Olivares-Galvan, J.C. ; Escarela-Perez, R. ; De León, F. ; Campero-Littlewood, E. ; Cruz, C. Aviles
Author_Institution :
Dept. de Energia, Univ. Autonoma Metropolitana, Mexico City, Mexico
Volume :
35
Issue :
1
fYear :
2010
Firstpage :
33
Lastpage :
39
Abstract :
The separation of eddy current and hysteresis losses in transformer cores is obtained using the two-temperatures and the two-frequency methods. Loss calculations for six ratings using the voltage test waveform ratio are included to compare and analyze results. A brief description of the test methodologies, that are easy to apply, is given. An example of the application of the methodologies, the obtained measurements and obtained results are included. In some cases, the results show that eddy current losses for the analyzed ratings are greater than 60% of no-load losses. Results include the impact of no-load losses in total owning cost of transformers.
Keywords :
eddy current losses; power transformers; transformer cores; core losses; distribution transformers; eddy current losses; experimental methods; hysteresis losses; loss separation; no-load losses; transformer cores; two-frequency methods; two-temperatures methods; voltage test waveform ratio; Core loss; Eddy currents; Frequency measurement; Lamination; Loss measurement; Magnetic hysteresis; Temperature measurement; distribution transformers; eddy current losses; hysteresis losses; iron-core losses; loss separation; no-load test; two-frequency method; two-temperature method;
fLanguage :
English
Journal_Title :
Electrical and Computer Engineering, Canadian Journal of
Publisher :
ieee
ISSN :
0840-8688
Type :
jour
DOI :
10.1109/CJECE.2010.5783382
Filename :
5783382
Link To Document :
بازگشت