Abstract :
Equivalent circuits based on the actual connection of coil-groups of generators are used to study the characteristics of various generator stator ground fault protection schemes presented in the literature. The evaluation and the comparison of the characteristics of those schemes are given by means of protection coverage-critical resistance curves. Although these schemes are successful in practice, they suffer the disadvantage of low sensitivity, which is strongly related to generator operating conditions. To overcome this disadvantage, two adaptive stator ground fault protection schemes based on digital techniques are developed. Compared to conventional third-harmonic voltage schemes, they can automatically track the change of generator operating conditions before a ground fault occurs. Test results from a digital simulation show that they can keep high sensitivity during all operating conditions
Keywords :
fault currents; harmonics; machine protection; synchronous generators; turbogenerators; adaptive stator ground fault protection schemes; coil-groups; digital techniques; stator ground fault protection schemes; third harmonic voltages; turbogenerator; Admittance; Capacitance; Character generation; Circuit faults; Equivalent circuits; Magnetic field measurement; Protection; Stator windings; Turbogenerators; Voltage;
fLanguage :
English
Journal_Title :
Power Delivery, IEEE Transactions on
Publisher :
ieee
ISSN :
0885-8977
Type :
jour
DOI :
10.1109/61.53061
Filename :
53061
Link To Document :
بازگشت