    Justification of Effective Reactive Power Reserves With Respect to a Particular Bus Using Linear Sensitivity

  • Author

    Choi, Y.H. ; Seo, S. ; Kang, S. ; Lee, B.

  • Author_Institution
    Dept. of Electr. Eng., Korea Univ., Seoul, South Korea
  • Volume
    26
  • Issue
    4
  • fYear
    2011
  • Firstpage
    2118
  • Lastpage
    2124
  • Abstract
    A constant reactive power (Q) reserve (CQR) is measured by the difference between the maximum reactive power generation and its current. However, all reactive power sources must not affect the entire power system when severe contingencies occur. Thus, generators must be evaluated as to whether or not they will have an impact on the maximum permissible loading of buses. This definition considers some generators to still have reactive power reserves when the system faces voltage collapse. This remaining reactive power reserve, although available, cannot be used in an arbitrary manner. This paper proposes the concept of an effective reactive power reserve and it is calculated on the basis of a sensitivity analysis. The computed reactive power reserve is analyzed using static and dynamic simulations in bulk power systems.
  • Keywords
    electric power generation; power system dynamic stability; reactive power; sensitivity analysis; bulk power system dynamic simulations; effective reactive power reserves; linear sensitivity analysis; maximum reactive power generation; reactive power sources; voltage collapse; Generators; Power system stability; Reactive power; Sensitivity; Stability criteria; Effective reactive power (Q) reserve (EQR); particular bus; reactive power reserve; sensitivity; voltage stability;
  • fLanguage
    English
  • Journal_Title
    Power Systems, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0885-8950
  • Type

    jour

  • DOI
    10.1109/TPWRS.2011.2151212
  • Filename