Justification of Effective Reactive Power Reserves With Respect to a Particular Bus Using Linear Sensitivity
Author
Choi, Y.H. ; Seo, S. ; Kang, S. ; Lee, B.
Author_Institution
Dept. of Electr. Eng., Korea Univ., Seoul, South Korea
Volume
26
Issue
4
fYear
2011
Firstpage
2118
Lastpage
2124
Abstract
A constant reactive power (Q) reserve (CQR) is measured by the difference between the maximum reactive power generation and its current. However, all reactive power sources must not affect the entire power system when severe contingencies occur. Thus, generators must be evaluated as to whether or not they will have an impact on the maximum permissible loading of buses. This definition considers some generators to still have reactive power reserves when the system faces voltage collapse. This remaining reactive power reserve, although available, cannot be used in an arbitrary manner. This paper proposes the concept of an effective reactive power reserve and it is calculated on the basis of a sensitivity analysis. The computed reactive power reserve is analyzed using static and dynamic simulations in bulk power systems.
Keywords
electric power generation; power system dynamic stability; reactive power; sensitivity analysis; bulk power system dynamic simulations; effective reactive power reserves; linear sensitivity analysis; maximum reactive power generation; reactive power sources; voltage collapse; Generators; Power system stability; Reactive power; Sensitivity; Stability criteria; Effective reactive power (Q) reserve (EQR); particular bus; reactive power reserve; sensitivity; voltage stability;
fLanguage
English
Journal_Title
Power Systems, IEEE Transactions on
Publisher
ieee
ISSN
0885-8950
Type
jour
DOI
10.1109/TPWRS.2011.2151212
Filename
5783533
Link To Document