• DocumentCode
    1535413
  • Title

    Complete characterization of utilization-voltage power system impedance using wideband measurement

  • Author

    Rhode, Jason P. ; Kelley, Arthur W. ; Baran, Mesut E.

  • Author_Institution
    Crystal Semicond. Corp., Austin, TX, USA
  • Volume
    33
  • Issue
    6
  • fYear
    1997
  • Firstpage
    1472
  • Lastpage
    1479
  • Abstract
    Inexpensive portable instrumentation is used to measure the impedance of an example utilization-voltage power system, With the power system in normal operation, line-to-neutral, line-to-ground and neutral-to-ground impedances are measured over a bandwidth of 20 Hz-24 kHz. The measured impedance is presented as resistance and inductance, which vary with frequency. Based on the measurements, additional calculations are performed to find the resistance and inductance of every conductor in the system. This complete wide-band characterization of power system impedance provides valuable data for power quality calculations
  • Keywords
    computerised instrumentation; electric impedance measurement; fault currents; portable instruments; power cables; power supply quality; power system measurement; 20 to 24 kHz; impedance measurements; portable instrumentation; power quality calculations; power system conductors; utilization-voltage power system impedance characterisation; wideband measurement; Bandwidth; Electrical resistance measurement; Frequency measurement; Impedance measurement; Inductance measurement; Instruments; Performance evaluation; Power measurement; Power system measurements; Power systems;
  • fLanguage
    English
  • Journal_Title
    Industry Applications, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0093-9994
  • Type

    jour

  • DOI
    10.1109/28.649958
  • Filename
    649958