DocumentCode
1535413
Title
Complete characterization of utilization-voltage power system impedance using wideband measurement
Author
Rhode, Jason P. ; Kelley, Arthur W. ; Baran, Mesut E.
Author_Institution
Crystal Semicond. Corp., Austin, TX, USA
Volume
33
Issue
6
fYear
1997
Firstpage
1472
Lastpage
1479
Abstract
Inexpensive portable instrumentation is used to measure the impedance of an example utilization-voltage power system, With the power system in normal operation, line-to-neutral, line-to-ground and neutral-to-ground impedances are measured over a bandwidth of 20 Hz-24 kHz. The measured impedance is presented as resistance and inductance, which vary with frequency. Based on the measurements, additional calculations are performed to find the resistance and inductance of every conductor in the system. This complete wide-band characterization of power system impedance provides valuable data for power quality calculations
Keywords
computerised instrumentation; electric impedance measurement; fault currents; portable instruments; power cables; power supply quality; power system measurement; 20 to 24 kHz; impedance measurements; portable instrumentation; power quality calculations; power system conductors; utilization-voltage power system impedance characterisation; wideband measurement; Bandwidth; Electrical resistance measurement; Frequency measurement; Impedance measurement; Inductance measurement; Instruments; Performance evaluation; Power measurement; Power system measurements; Power systems;
fLanguage
English
Journal_Title
Industry Applications, IEEE Transactions on
Publisher
ieee
ISSN
0093-9994
Type
jour
DOI
10.1109/28.649958
Filename
649958