The effect of DC offset on instantaneous operating characteristics of low-voltage circuit breakers
Author :
Chapman, Francis X. ; Hammonds, Bret
Author_Institution :
SPD Technol., Philadelphia, PA, USA
Volume :
33
Issue :
6
fYear :
1997
Firstpage :
1488
Lastpage :
1492
Abstract :
This paper addresses the effect of asymmetrical currents on factory adjustments and field verification of low-voltage circuit breaker instantaneous trip units. Both molded case circuit breakers (MCCBs) and power circuit breakers are pertinent. Factory adjustment of low-voltage circuit breakers, based on test results using asymmetrical current, may cause the circuit breaker instantaneous unit to perform improperly and result in inadequate protection and coordination of electrical system apparatus. Similarly, field testing conducted to verify proper performance of low-voltage circuit breakers, using asymmetrical current, may lead to the erroneous conclusion that the circuit breaker´s instantaneous unit is out of specification. In addition to addressing the difficulties presented by this phenomenon, this paper also proposes an approach to identifying and overcoming these testing difficulties
Keywords :
circuit breakers; harmonic distortion; power system harmonics; switchgear testing; DC offset effect; asymmetrical currents; instantaneous operating characteristics; instantaneous unit; low-voltage circuit breaker; low-voltage circuit breakers; molded case circuit breakers; power circuit breakers; test results; testing difficulties; Circuit breakers; Circuit faults; Circuit testing; Fault diagnosis; Industry Applications Society; Isolation technology; Performance evaluation; Power system protection; Production facilities; System testing;
fLanguage :
English
Journal_Title :
Industry Applications, IEEE Transactions on
Publisher :
ieee
ISSN :
0093-9994
Type :
jour
DOI :
10.1109/28.649960
Filename :
649960
Link To Document :
بازگشت