• DocumentCode
    1535998
  • Title

    Steep front impulse flashover tests on a solid-state relay

  • Author

    Salas, T.M. ; Wiggins, C.M. ; Barnes, P.R.

  • Author_Institution
    BDM Int. Inc., Albuquerque, NM, USA
  • Volume
    5
  • Issue
    3
  • fYear
    1990
  • fDate
    7/1/1990 12:00:00 AM
  • Firstpage
    1281
  • Lastpage
    1287
  • Abstract
    A protective relay system, subjected to a high-voltage, steep-front impulse, has been shown to fail in the laboratory via flashover-induced current follow through on the DC power supply. Laboratory experiments were performed to characterize the response of a protective relay to steep-front impulses. These impulses may be the result of a nuclear-induced, high-altitude electromagnetic pulse. Tests were also conducted to quantify the protection offered by a surge protection package on the DC circuits of a relay system. Results from these tests were used to assess the vulnerability of a protective relay
  • Keywords
    electromagnetic pulse; flashover; high-voltage techniques; impulse testing; laboratory apparatus and techniques; power system protection; relay protection; surge protection; switchgear testing; DC power supply; electromagnetic pulse; high-voltage; impulse flashover tests; power system relay protection; response; solid-state relay; steep-front impulse; surge protection; switchgear testing; vulnerability; Circuit testing; Flashover; Impulse testing; Laboratories; Power supplies; Power system protection; Power system relaying; Protective relaying; Relays; Solid state circuits;
  • fLanguage
    English
  • Journal_Title
    Power Delivery, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0885-8977
  • Type

    jour

  • DOI
    10.1109/61.57967
  • Filename