DocumentCode :
1535998
Title :
Steep front impulse flashover tests on a solid-state relay
Author :
Salas, T.M. ; Wiggins, C.M. ; Barnes, P.R.
Author_Institution :
BDM Int. Inc., Albuquerque, NM, USA
Volume :
5
Issue :
3
fYear :
1990
fDate :
7/1/1990 12:00:00 AM
Firstpage :
1281
Lastpage :
1287
Abstract :
A protective relay system, subjected to a high-voltage, steep-front impulse, has been shown to fail in the laboratory via flashover-induced current follow through on the DC power supply. Laboratory experiments were performed to characterize the response of a protective relay to steep-front impulses. These impulses may be the result of a nuclear-induced, high-altitude electromagnetic pulse. Tests were also conducted to quantify the protection offered by a surge protection package on the DC circuits of a relay system. Results from these tests were used to assess the vulnerability of a protective relay
Keywords :
electromagnetic pulse; flashover; high-voltage techniques; impulse testing; laboratory apparatus and techniques; power system protection; relay protection; surge protection; switchgear testing; DC power supply; electromagnetic pulse; high-voltage; impulse flashover tests; power system relay protection; response; solid-state relay; steep-front impulse; surge protection; switchgear testing; vulnerability; Circuit testing; Flashover; Impulse testing; Laboratories; Power supplies; Power system protection; Power system relaying; Protective relaying; Relays; Solid state circuits;
fLanguage :
English
Journal_Title :
Power Delivery, IEEE Transactions on
Publisher :
ieee
ISSN :
0885-8977
Type :
jour
DOI :
10.1109/61.57967
Filename :
57967
Link To Document :
بازگشت