• DocumentCode
    1536085
  • Title

    Interruption ability of a self extinguishing type gas circuit breaker

  • Author

    Arita, H. ; Natsui, K. ; Tsukushi, M. ; Kurosawa, Y. ; Hirasawa, K.

  • Author_Institution
    Hitachi Ltd., Ibaraki, Japan
  • Volume
    5
  • Issue
    3
  • fYear
    1990
  • fDate
    7/1/1990 12:00:00 AM
  • Firstpage
    1362
  • Lastpage
    1369
  • Abstract
    Interruption ability of a self-extinguishing-type gas circuit breaker has been investigated while varying several structural factors. With a thermal puffer cylinder (0.7 l volume), excellent interruption ability (9.5 to 31.5 kA at 84 kV) was obtained for the condition of a breaker-terminal fault (BTF). In the condition of a short-line fault (SLF), however, its interruptible arcing time width at the same current levels was only 0.2 to 0.3 cycles, where 0.5 cycles was proposed. The critical current, which is the minimum current which the breaker can interrupt, was several kiloamperes
  • Keywords
    electrical faults; gas blast circuit breakers; switchgear testing; 84 kV; 9.5 to 31.5 kA; breaker-terminal fault; interruption ability; self extinguishing type gas circuit breaker; short-line fault; structural factors; switchgear testing; Circuit breakers; Circuit faults; Circuit testing; Critical current; Hydraulic actuators; Interrupters; Power generation economics; Power system reliability; Springs; Voltage;
  • fLanguage
    English
  • Journal_Title
    Power Delivery, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0885-8977
  • Type

    jour

  • DOI
    10.1109/61.57978
  • Filename
    57978