Title :
Aging of composite insulators: simulation by electrical tests
Author :
de Tourreil, C.H. ; Lambeth, P.J.
Author_Institution :
IREQ, Varennes, Que., Canada
fDate :
7/1/1990 12:00:00 AM
Abstract :
To assess the long term performance of 72 kV and 230 kV composite long rod insulators, different laboratory aging tests have been developed. Two principal diagnostic tests were used to measure the performance of the insulators, the quick flashover salt-fog (QFO SF), and the rapid flashover clean-fog (RFO CF) tests. The following aging processes were used: cement coating and clean-fog, salt fog, and cement coating and salt fog. Similar sets of insulators were also aged in the field for over three years, and all the insulators were evaluated in the laboratory. The cement/salt-fog aging process was found to be the most controllable and realistic after the results were assessed by means of the RFO CF test
Keywords :
ageing; composite insulating materials; flashover; insulation testing; insulators; 230 kV; 72 kV; aging; cement coating; composite insulators; diagnostic tests; electrical tests; long rod insulators; quick flashover salt fog test; rapid flashover clean fog test; simulation; Aging; Coatings; Corona; Dielectrics and electrical insulation; Flashover; Insulator testing; Laboratories; Manufacturing; North America; Pollution measurement;
Journal_Title :
Power Delivery, IEEE Transactions on