DocumentCode :
1536359
Title :
Investigation of the insulation performance of the insulator covered with Lichen
Author :
Naito, K. ; Matsuoka, R. ; Sakanishi, K.
Author_Institution :
NGK Insulators Ltd., Nagoya, Japan
Volume :
5
Issue :
3
fYear :
1990
fDate :
7/1/1990 12:00:00 AM
Firstpage :
1634
Lastpage :
1640
Abstract :
The results of an investigation of the dielectric strength of lichen-contaminated insulators removed from actual transmission lines of three different countries are reported. All of the insulators showed low equivalent salt-deposit density. It seems that lichen on its own cannot cause flashover of the insulators. Flashover may be caused only if the thickness of the lichen is very great and/or there is superposition of salt
Keywords :
electric strength; flashover; insulators; Lichen; dielectric strength; flashover; insulation performance; insulator; lichen-contaminated insulators; low equivalent salt-deposit density; transmission lines; Algae; Conducting materials; Dielectrics and electrical insulation; Flashover; Fungi; Power transmission lines; Production facilities; Sea surface; Surface contamination; Voltage;