  • Abstract
    The results of an investigation of the dielectric strength of lichen-contaminated insulators removed from actual transmission lines of three different countries are reported. All of the insulators showed low equivalent salt-deposit density. It seems that lichen on its own cannot cause flashover of the insulators. Flashover may be caused only if the thickness of the lichen is very great and/or there is superposition of salt
  • Keywords
    electric strength; flashover; insulators; Lichen; dielectric strength; flashover; insulation performance; insulator; lichen-contaminated insulators; low equivalent salt-deposit density; transmission lines; Algae; Conducting materials; Dielectrics and electrical insulation; Flashover; Fungi; Power transmission lines; Production facilities; Sea surface; Surface contamination; Voltage;