DocumentCode
1536478
Title
NERC´s new control performance standards
Author
Jaleeli, N.
Author_Institution
Priority-Based Control Eng., Dublin, OH
Volume
14
Issue
3
fYear
1999
fDate
8/1/1999 12:00:00 AM
Firstpage
1092
Lastpage
1099
Abstract
For several decades, control area performance in normal interconnected power system operation has been assessed by Criteria A 1 and A2. On February 1, 1997, the North American Electric Reliability Council (NERC) replaced A1 and A2 with control performance standards CPS1 and CPS2. These criteria, or standards, assess characteristics of an area´s “area control error”. Their purpose is to indicate whether an area´s generation is adequately controlled to make interchange meet its schedule and interconnection frequency support obligation. After January 1998, control areas are expected to be at least 100% in compliance with CPS1 and 90% with CPS2. There will be sanctions for areas failing to meet these standards. This paper briefly describes the new control performance standards, their technical foundations and the research leading to them
Keywords
power system control; power system interconnection; power system reliability; standards; NERC power system control performance standards; North American Electric Reliability Council; area control error; control area performance; frequency support obligation.; interconnected power system operation; technical foundations; Area measurement; Centralized control; Control engineering; Control systems; Error correction; Frequency; Interconnected systems; Power system control; Power system interconnection; Power systems;
fLanguage
English
Journal_Title
Power Systems, IEEE Transactions on
Publisher
ieee
ISSN
0885-8950
Type
jour
DOI
10.1109/59.780932
Filename
780932
Link To Document