DocumentCode :
1536811
Title :
Analysis of line compensation by shunt-connected FACTS controllers: a comparison between SVC and STATCOM
Author :
Tan, Y.L.
Author_Institution :
Nanyang Technol. Inst., Singapore
Volume :
19
Issue :
8
fYear :
1999
fDate :
8/1/1999 12:00:00 AM
Firstpage :
57
Lastpage :
58
Abstract :
A novel method for the analysis of the effectiveness of an SVC and a STATCOM of the same kVAr rating for first-swing stability enhancement is presented and the concept is demonstrated with a numerical example. The analysis shows that the STATCOM is superior to the SVC for first-swing stability enhancement
Keywords :
flexible AC transmission systems; power system control; power system stability; static VAr compensators; STATCOM; SVC; first-swing stability enhancement; line compensation analysis; shunt-connected FACTS controllers; static VAr compensators; static synchronous compensator; Automatic voltage control; Control systems; Inductors; Power system modeling; Power system stability; Power system transients; Shunt (electrical); Stability analysis; Static VAr compensators; Thyristors;
fLanguage :
English
Journal_Title :
Power Engineering Review, IEEE
Publisher :
ieee
ISSN :
0272-1724
Type :
jour
DOI :
10.1109/39.780992
Filename :
780992
Link To Document :
بازگشت