DocumentCode :
1538580
Title :
Vacuum interrupter model based on breaking tests
Author :
Leusenkamp, Martin B J
Author_Institution :
HOLEC Middenspanning B.V., Hengelo, Netherlands
Volume :
27
Issue :
4
fYear :
1999
fDate :
8/1/1999 12:00:00 AM
Firstpage :
969
Lastpage :
976
Abstract :
In this paper, a model will be presented of a HOLEC-made commercially available vacuum interrupter. This model can he used to determine the breaking capacity under various current switching conditions. It will be shown how the model is derived from switching tests in a synthetic test circuit. The measured data consist mainly of short circuit currents, arc voltages, TRV´s, and arcing times from which other important information like, e.g., the critical arc energy and the amount of transferred electric charge can be determined. The calculated results obtained by the theoretical model and the measured data will be shown in various graphs. Furthermore, derating curves of this type of vacuum interrupter and a comparison between different types of electrode configurations will be presented
Keywords :
electric charge; short-circuit currents; vacuum circuit breakers; vacuum interrupters; DC component; Weil-Dobke circuit; arc voltage; arcing times; axial magnetic field; breaking capacity; breaking tests; critical arc energy; current switching conditions; derating curve; electrode configurations; horseshoe electrodes; short circuit current; synthetic test circuit; transferred electric charge; vacuum interrupter; vacuum interrupter model; Charge measurement; Circuit testing; Current measurement; Electric variables measurement; Electrodes; Energy measurement; Interrupters; Short circuit currents; Switching circuits; Voltage;
fLanguage :
English
Journal_Title :
Plasma Science, IEEE Transactions on
Publisher :
ieee
ISSN :
0093-3813
Type :
jour
DOI :
10.1109/27.782268
Filename :
782268
Link To Document :