• DocumentCode
    1540997
  • Title

    The impact of public lighting on voltage distortion in low voltage distribution systems

  • Author

    Bompard, Ettore ; Carpaneto, Enrico ; Chicco, Gianfranco ; Ribaldone, Paolo ; Vercellino, Claudio

  • Author_Institution
    Dipartimento di Ingegneria Elettrica Ind., Politecnico di Torino, Italy
  • Volume
    16
  • Issue
    4
  • fYear
    2001
  • fDate
    10/1/2001 12:00:00 AM
  • Firstpage
    752
  • Lastpage
    757
  • Abstract
    Harmonic distortion has become a main concern in electric distribution systems. Several public utilities are experiencing harmonic problems on their networks and some of them started to monitor the situation of the MV and LV distribution networks. The operation of the MV and LV networks of the AEM-Torino (the city utility) has been investigated with several on-site measurements. The survey led to the observation of a step increase in voltage distortion on LV feeder when the city street lighting is switched on and, vice versa, a sudden decrease when it is switched off. This phenomenon can be mainly traced back to the resonance, under certain conditions, between the capacitance of the capacitors for the improvement of the lamps power factor and the inductance of the MV/LV transformer. This work investigates the phenomenon both from a theoretical point and with laboratory and field tests. Some possible remedies and their practical implementation to reduce harmonic distortion are discussed
  • Keywords
    capacitance; distribution networks; harmonic distortion; harmonics suppression; power system harmonics; street lighting; AEM; LV distribution networks; LV feeder; MV distribution networks; MV/LV transformer; Torino; capacitance; electric distribution systems; harmonic distortion reduction; harmonic problems; inductance; low voltage distribution systems; on-site measurements; public lighting; resonance; street lighting switch-off; street lighting switch-on; voltage distortion; Capacitance; Capacitors; Cities and towns; Distortion measurement; Harmonic distortion; LED lamps; Low voltage; Monitoring; Reactive power; Resonance;
  • fLanguage
    English
  • Journal_Title
    Power Delivery, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0885-8977
  • Type

    jour

  • DOI
    10.1109/61.956766
  • Filename
    956766