• DocumentCode
    1544129
  • Title

    Evaluation of pulling rope wear and coefficient of friction for pipe-type cables

  • Author

    Bascom, E.C. ; Stewart, J.R. ; Tang, L.Y.

  • Author_Institution
    Power Technol. Inc., Schenectady, NY, USA
  • Volume
    12
  • Issue
    2
  • fYear
    1997
  • fDate
    4/1/1997 12:00:00 AM
  • Firstpage
    542
  • Lastpage
    546
  • Abstract
    The coefficient of friction between the pulling rope and cable pipe for a high-pressure fluid-filled cable was determined in order to characterize the effects of pulling tension and sidewall pressure on this parameter. Pipe wear was also measured. The study found that variations in pulling tension were more strongly affected by pulling rope wear than pipe wear. The coefficient of friction of the pulling rope varied from 0.27 to 0.75. Pipe wear of 1.52 mm (60 mils) was measured during 430 m (1425 ft.) of pulls at 1414 kgf/m (950 lbs./ft.) sidewall pressure and 1.02 mm (40 mils) of wear was measured during 290 m (950 ft.) of pulls at 610 kgf/m (410 lbs./ft.) sidewall pressure
  • Keywords
    cable laying; electric conduits; friction; insulating oils; mechanical variables measurement; power cable insulation; power cable testing; power cables; wear testing; 1414 kgf/m2; 290 m; 430 m; 610 kgf/m2; coefficient of friction; high-pressure fluid-filled cable; pipe wear measurement; pipe-type cables; pulling rope wear; pulling tension; sidewall pressure; Aluminum; Cables; Conducting materials; Force measurement; Friction; Pressure measurement; Pulleys; Steel; Testing; Winches;
  • fLanguage
    English
  • Journal_Title
    Power Delivery, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0885-8977
  • Type

    jour

  • DOI
    10.1109/61.584318
  • Filename
    584318