DocumentCode :
1544161
Title :
High voltage VLF testing of power cables
Author :
Eager, G.S. ; Katz, C. ; Fryszczyn, B. ; Densley, J. ; Bernstein, B.S.
Author_Institution :
Cable Technol. Labs. Inc., New Brunswick, NJ, USA
Volume :
12
Issue :
2
fYear :
1997
fDate :
4/1/1997 12:00:00 AM
Firstpage :
565
Lastpage :
570
Abstract :
This publication describes a laboratory test program conducted with the objective to develop a test that would replace the existing DC withstand test. The article describes the methodology used to establish the voltage duration and magnitude of VLF (0.1 Hz) high voltage field tests suitable for crosslinked polyethylene (XLPE) insulated power cable. The results show that the voltage breakdown of laboratory aged XLPE cable at 0.1 Hz is approximately equal to that at 60 Hz, that proof tests at 0.1 Hz cause very little damage to the cable, and that 0.1 Hz testing appears to be a satisfactory alternate to DC testing. Preliminary values are suggested for voltage magnitude and time duration of cable acceptance, maintenance and proof tests at 0.1 Hz for XLPE cable rated up to 35 kV. A program is underway to similarly evaluate samples of service-aged XLPE cable; as well as to demonstrate the use of the preliminary test values at typical utility installations
Keywords :
XLPE insulation; ageing; electric breakdown; insulation testing; power cable insulation; power cable testing; 0.1 Hz; 35 kV; XLPE insulated power cable; cable acceptance; cable maintenance; crosslinked polyethylene; high voltage VLF testing; laboratory aged XLPE cable; power cables; proof tests; service-aged XLPE cable; voltage breakdown; voltage duration; Aging; Breakdown voltage; Dielectric breakdown; Power cables; Power generation; Shape; Signal generators; Stress; Testing; Trees - insulation;
fLanguage :
English
Journal_Title :
Power Delivery, IEEE Transactions on
Publisher :
ieee
ISSN :
0885-8977
Type :
jour
DOI :
10.1109/61.584323