Controlled closing on shunt reactor compensated transmission lines. II. Application of closing control device for high-speed autoreclosing on BC Hydro 500 kV transmission line
Author :
Froehlich, K. ; Hoelzl, C. ; Stanek, M. ; Carvalho, A.C. ; Hofbauer, W. ; Hoegg, P. ; Avent, B.L. ; Peelo, D.F. ; Sawada, J.H.
Author_Institution :
Tech. Univ. Wien, Austria
Volume :
12
Issue :
2
fYear :
1997
fDate :
4/1/1997 12:00:00 AM
Firstpage :
741
Lastpage :
746
Abstract :
In the past, BC Hydro used circuit breaker closing resistors to limit switching surges on its 500 kV transmission system. This approach was considered undesirable for new transmission lines and an innovative scheme incorporating special transmission line surge arresters and controlled high-speed autoreclosing of the circuit breaker was developed. The scheme and its basis as applied on a new 330 km long 500 kV transmission line are described. Actual line switching tests, also described, confirmed the validity of the studies performed and applied design concepts, and the value of the scheme
Keywords :
arresters; circuit breakers; power system protection; power transmission lines; transmission networks; 330 km; 500 kV; EHV transmission lines; closing control device; design concepts; high-speed autoreclosing; line switching tests; protection performance; shunt reactor-compensated transmission lines; surge arresters; Arresters; Circuit breakers; Circuit testing; Distributed parameter circuits; Inductors; Resistors; Shunt (electrical); Surges; Switching circuits; Transmission lines;
fLanguage :
English
Journal_Title :
Power Delivery, IEEE Transactions on
Publisher :
ieee
ISSN :
0885-8977
Type :
jour
DOI :
10.1109/61.584360
Filename :
584360
Link To Document :
بازگشت