DocumentCode :
1544391
Title :
Minimizing harmonic voltage distortion with multiple current-constrained active power line conditioners
Author :
Chang, W.K. ; Grady, W.M.
Author_Institution :
Siemens Empros, Brooklyn Park, MN, USA
Volume :
12
Issue :
2
fYear :
1997
fDate :
4/1/1997 12:00:00 AM
Firstpage :
837
Lastpage :
843
Abstract :
The purpose of this paper is to present a useful algorithm for minimizing harmonic voltage distortion levels with multiple current-constrained active power line conditioners (APLCs) in a power system. The algorithm contains a sensitivity analysis-based single-APLC placement procedure, and uses a nonlinear programming optimizer GRG2 to improve the solution if necessary. The usefulness of this algorithm is then illustrated by a distribution system example. Simulation results show that the algorithm is simple, computationally efficient and can be easily extended to minimize several other alternative harmonic-related network objective functions
Keywords :
harmonic distortion; minimisation; nonlinear programming; power system analysis computing; power system harmonics; sensitivity analysis; active power line conditioners; algorithm; computational efficiency; distribution system; harmonic voltage distortion minimisation; nonlinear programming optimizer; objective functions; placement procedure; power systems; sensitivity analysis; Algorithm design and analysis; Analytical models; Computational modeling; Functional programming; Harmonic analysis; Harmonic distortion; Power system analysis computing; Power system harmonics; Power system simulation; Voltage;
fLanguage :
English
Journal_Title :
Power Delivery, IEEE Transactions on
Publisher :
ieee
ISSN :
0885-8977
Type :
jour
DOI :
10.1109/61.584402
Filename :
584402
Link To Document :
بازگشت