DocumentCode
1544565
Title
Outdoor polymeric insulators long-term exposed to HVDC
Author
Sorqvis, Torbjoörn ; Vlastos, A.E.
Author_Institution
Dept. of High Voltage Eng., Chalmers Univ. of Technol., Gothenburg, Sweden
Volume
12
Issue
2
fYear
1997
fDate
4/1/1997 12:00:00 AM
Firstpage
1041
Lastpage
1048
Abstract
Field experience from outdoor polymeric insulators exposed to HVDC under natural contamination conditions is presented. This paper summarizes the peak leakage current statistics, the hydrophobicity and the surface material conditions studied by electron spectroscopy for chemical analysis (ESCA) and attenuated total reflection Fourier transform infrared (ATR-FTIR) spectroscopy. The results show a strong interrelation between the surface conditions and the performance with respect to leakage currents. Moreover, the results show that the surface conditions and the performance of the insulators exposed to HVDC are rather similar to those of the insulators exposed to HVAC
Keywords
HVDC power transmission; ageing; electric breakdown; electric current measurement; insulator testing; leakage currents; polymer insulators; attenuated total reflection Fourier transform infrared spectroscopy; electron spectroscopy for chemical analysis; hydrophobicity; insulation breakdown testing; insulator performance; long-term HVDC exposure; natural contamination conditions; outdoor polymeric insulators; peak leakage current; surface material conditions; Chemical analysis; Electrons; HVDC transmission; Infrared spectra; Leakage current; Plastic insulation; Polymers; Spectroscopy; Statistical analysis; Surface contamination;
fLanguage
English
Journal_Title
Power Delivery, IEEE Transactions on
Publisher
ieee
ISSN
0885-8977
Type
jour
DOI
10.1109/61.584435
Filename
584435
Link To Document