Title :
Considerations for generator ground-fault protection in midsize cogeneration plants
Author :
Rifaat, Rasheek M.
Author_Institution :
Delta Hudson Eng. Ltd., Calgary, Alta., Canada
Abstract :
Generator ground-fault protection aspects are analyzed for midsize cogeneration plants. In these plants, the generators may be connected to a common generator bus. The overall bus-connected system should be considered when applying generator high-resistance grounding schemes. Calculations are reviewed for sizing generator neutral-ground resistance and evaluating third harmonic originated in the scheme. The relevant applications of third harmonics in applying 100% stator ground-fault protection schemes are examined. Practical considerations are presented for establishing selectivity of ground-fault protection schemes in the case of a common generator bus
Keywords :
cogeneration; earthing; electric generators; electric resistance; electrical faults; harmonics; machine protection; stators; bus-connected system; common generator bus; generator ground-fault protection; ground-fault protection selectivity; high-resistance grounding; midsize cogeneration plants; neutral-ground resistance sizing; stator ground-fault protection; third harmonic evaluation; Cogeneration; Digital relays; Electric resistance; Grounding; Power generation; Power system harmonics; Power system protection; Power transformer insulation; Protective relaying; Stators;
Journal_Title :
Industry Applications, IEEE Transactions on