• DocumentCode
    1549111
  • Title

    Sparkover in the rod-plane gap under composite slow front positive impulse/alternating voltages

  • Author

    Allen, N.L. ; Huang, C.F.

  • Author_Institution
    Centre for Electr. Energy, Univ. of Manchester Inst. of Sci. & Technol., UK
  • Volume
    146
  • Issue
    3
  • fYear
    1999
  • fDate
    5/1/1999 12:00:00 AM
  • Firstpage
    142
  • Lastpage
    146
  • Abstract
    Problems are discussed which relate to the measurement of the sparkover voltage of an airgap under a composite voltage comprising an impulse superimposed on an alternating voltage. The rod-plane gap has been taken as an example. Sparkover values have been measured with the impulse generator fired at angles 0°, 90°, 180° and 270° in the alternating cycle. Tests have also been made with firing at random angles. Sparkover voltages do not differ significantly from those for simple impulse alone, except for the case of random firing, where a small apparent increase occurs. It is shown that the `up and down´ method of measurement is satisfactory where specific firing angles are used, but is unsatisfactory and misleading where firing is at random angles
  • Keywords
    air gaps; corona; electric strength; high-voltage techniques; overvoltage; HV circuit; air gap; composite slow front positive impulse/alternating voltages; corona effects; firing at random angles; rod-plane gap; sparkover; up and down measurement method;
  • fLanguage
    English
  • Journal_Title
    Science, Measurement and Technology, IEE Proceedings -
  • Publisher
    iet
  • ISSN
    1350-2344
  • Type

    jour

  • DOI
    10.1049/ip-smt:19990024
  • Filename
    785310