Sharing of nonlinear load in parallel-connected three-phase converters
Author :
Borup, Uffe ; Blaabjerg, Frede ; Enjeti, Prasad N.
Author_Institution :
AXA Power, Odense, Denmark
Volume :
37
Issue :
6
fYear :
2001
Firstpage :
1817
Lastpage :
1823
Abstract :
In this paper, a new control method is presented which enables equal sharing of linear and nonlinear loads in three-phase power converters connected in parallel, without communication between the converters. The paper focuses on solving the problem that arises when two converters with harmonic compensation are connected in parallel. Without the new solution, they are normally not able to distinguish the harmonic currents that flow to the load and harmonic currents that circulate between the converters. Analysis and experimental results on two 90-kVA 400-Hz converters in parallel are presented. The results show that both linear and nonlinear loads can be shared equally by the proposed concept
Keywords :
compensation; control system analysis; control system synthesis; harmonic distortion; harmonics suppression; load (electric); power conversion harmonics; power supply quality; reactive power control; 400 Hz; 90 kVA; control design; control method; control performance; control simulation; ground power units; harmonic compensation; harmonic currents; harmonic distortion; nonlinear load sharing; parallel-connected three-phase power converters; Communication system control; Frequency conversion; Linear feedback control systems; Pi control; Power system harmonics; Power system reliability; Proportional control; Reactive power; Uninterruptible power systems; Voltage control;
fLanguage :
English
Journal_Title :
Industry Applications, IEEE Transactions on
Publisher :
ieee
ISSN :
0093-9994
Type :
jour
DOI :
10.1109/28.968196
Filename :
968196
Link To Document :
بازگشت