• DocumentCode
    1551464
  • Title

    Reliability calculation of MV-distribution networks with regard to ageing in XLPE-insulated cables

  • Author

    Stötzel, M. ; Zdrallek, M. ; Wellssow, W.H.

  • Author_Institution
    Siegen Univ., Germany
  • Volume
    148
  • Issue
    6
  • fYear
    2001
  • fDate
    11/1/2001 12:00:00 AM
  • Firstpage
    597
  • Lastpage
    602
  • Abstract
    Failure statistics of German utilities show that more than 80% of the supply interruptions of medium voltage (MV) customers are caused by component outages located in the MV network itself. For these networks a model as near to reality as possible is required to correctly determine customers´ quality of supply. One aspect so far neglected in reliability calculations of MV networks is that the failure rate of most components is not constant for the whole lifetime, but rises over the years according to the increasing right wing of the well-known bathtub curve. Due to the water-treeing phenomenon, XLPE-insulated MV cables manufactured during the 1970s show heavy ageing problems after some years of operation, resulting in a strongly increasing failure rate. An approach is presented to take these increasing failure rates into account in reliability calculations of MV networks. The cable-failure models used in the investigation are described in detail as well as the data received from a special evaluation of the VDLW-statistics of XLPE-insulated MV cables reflecting the ageing phenomenon. Several calculations of an actual 10 kV cable network supplying parts of a German city are presented to show the impact of increasing cable failure rates on the reliability of MV customers´ power supply
  • Keywords
    XLPE insulation; ageing; power cable insulation; power distribution lines; power distribution reliability; transmission network calculations; 10 kV; German city; German utilities; MV network; XLPE-insulated MV cables; bathtub Curve; cable-failure models; component outages; failure rate; failure statistics; medium voltage customers; power supply reliability; reliability calculations; supply interruptions; water-treeing phenomenon;
  • fLanguage
    English
  • Journal_Title
    Generation, Transmission and Distribution, IEE Proceedings-
  • Publisher
    iet
  • ISSN
    1350-2360
  • Type

    jour

  • DOI
    10.1049/ip-gtd:20010505
  • Filename
    968481