DocumentCode :
1551639
Title :
Effects of Conductor Counter-Transposition on the Positive-Sequence Impedance and Losses of Cross-Bonded Cables
Author :
De León, Francisco ; Márquez-Asensio, Manuel L. ; Álvarez-Cordero, Gabriel
Author_Institution :
Polytech. Inst., New York Univ., New York, NY, USA
Volume :
26
Issue :
3
fYear :
2011
fDate :
7/1/2011 12:00:00 AM
Firstpage :
2060
Lastpage :
2063
Abstract :
In this letter, we show that contrary to common belief, counter-transposing the conductors when power cables are cross-bonded can increase the positive-sequence resistance by close to 20%. This is very important because the losses of a power cable are determined (for balanced operation) from the Joule loasses caused by the positive-sequence resistance (3R1I12).
Keywords :
conductors (electric); losses; power cables; Joule loasses; conductors; counter transposition; cross-bonded cables; positive-sequence resistance; power cables; Cable shielding; Conductors; Equations; Impedance; Power cables; Resistance; Wires; Ampacity; cable parameters; cables; cross-bonding; losses; positive-sequence impedance; resistance;
fLanguage :
English
Journal_Title :
Power Delivery, IEEE Transactions on
Publisher :
ieee
ISSN :
0885-8977
Type :
jour
DOI :
10.1109/TPWRD.2011.2123473