Risk factors regarding the application of degraded voltage relaying at nuclear. generating stations
Author
Kueck, J.D. ; Attarian, G.E. ; Leake, H.C. ; Sims, T.R.
Author_Institution
Oak Ridge Nat. Lab., TN, USA
Volume
16
Issue
4
fYear
2001
fDate
12/1/2001 12:00:00 AM
Firstpage
374
Lastpage
379
Abstract
Nuclear generating stations utilize degraded voltage relaying schemes to protect electrical equipment against sustained low voltage conditions. Based on regulatory guidance, typical design involves the use of undervoltage relays which, when actuated, automatically disconnect the safety buses from the degraded offsite power supply and initiate reconnection to an alternate supply such as the diesel-generator. This automatic disconnection creates the risk of an unwanted separation from the offsite power supply. Although the industry recognizes the importance of ensuring that adequate voltage is supplied to critical plant equipment, the method of achieving this goal is a matter of ongoing discussion. The potential benefits of degraded voltage relaying schemes do not necessarily outweigh the additional risks that they create, and other measures not explicitly described in the regulations, including detailed analyzes of the transmission grid and onsite distribution system, and procedural controls, are essential elements of a reliable offsite power supply
Keywords
diesel-electric generators; fission reactor safety; nuclear power stations; power generation protection; power system relaying; relay protection; risk management; standby generators; alternate supply reconnection; critical plant equipment; degraded offsite power supply; degraded voltage relaying application; degraded voltage relaying schemes; diesel-generator; electrical equipment protection; nuclear generating stations; onsite distribution system; risk factors; safety buses; sustained low voltage conditions; transmission grid; undervoltage relays; Degradation; Electricity supply industry; Low voltage; Nuclear power generation; Power supplies; Power system reliability; Protection; Protective relaying; Relays; Safety;
fLanguage
English
Journal_Title
Energy Conversion, IEEE Transactions on
Publisher
ieee
ISSN
0885-8969
Type
jour
DOI
10.1109/60.969478
Filename
969478
Link To Document