DocumentCode
1553170
Title
Method for rating power cables buried in surface troughs
Author
Lewin, P.L. ; Theed, J.E. ; Davies, A.E. ; Larsen, S.T.
Author_Institution
Dept. of Electr. Eng., Southampton Univ., UK
Volume
146
Issue
4
fYear
1999
fDate
7/1/1999 12:00:00 AM
Firstpage
360
Lastpage
364
Abstract
An alternative method is detailed by which the ambient temperature parameter as applied to the calculation of ratings of power cables buried in surface trough installations can be determined. Improvement in the accuracy of cable rating calculations will allow greater utilisation of the cable asset and assist for example in the planning of system outages for maintenance work. The proposed model calculates the temperature at the cable burial depth based on measurements of solar radiation, windspeed and air temperature. The model is based on physical laws rather than empirical approaches that have been shown to be generally conservative in application. Results based on weather data monitored over a two-year period show that the ambient temperature of the soil at cable depth can be accurately determined and the model provides a significant improvement on existing methods
Keywords
power cables; soil; thermal analysis; underground cables; air temperature; ambient temperature parameter; buried power cables rating method; rating calculation accuracy; soil temperature; solar radiation; surface trough installations; windspeed;
fLanguage
English
Journal_Title
Generation, Transmission and Distribution, IEE Proceedings-
Publisher
iet
ISSN
1350-2360
Type
jour
DOI
10.1049/ip-gtd:19990360
Filename