DocumentCode :
1553735
Title :
More sophisticated synchronous machine model and the relevant harmonic power flow study
Author :
Chen, H. ; Long, Y. ; Zhang, X.-P.
Author_Institution :
Dept. of Electr. Eng., Southeast Univ., Nanjing, China
Volume :
146
Issue :
3
fYear :
1999
fDate :
5/1/1999 12:00:00 AM
Firstpage :
261
Lastpage :
268
Abstract :
A more sophisticated Park equation-based synchronous machine model, used in harmonic load flow study, is proposed. From the physical interpretation of this model, it can be noticed that synchronous machines should also be considered as harmonic sources in power flow study, only if the power network is asymmetrical. This model is then incorporated with the extended `decoupling-compensation´ network model used for harmonic power flow analysis. Several cases are studied, including harmonics caused by asymmetry of transmission lines and nonlinear elements like static VAr compensators (SVCs). A computed result verifies the effectiveness of the proposed model and the conclusion that more sophisticated synchronous machine models should be employed to obtain the correct, full scenario of harmonics distribution in power system is drawn
Keywords :
harmonic distortion; load flow; machine theory; power system harmonics; power transmission lines; static VAr compensators; synchronous machines; Park equation; decoupling-compensation network model; harmonic power flow study; harmonics distribution; static VAr compensators; synchronous machine model;
fLanguage :
English
Journal_Title :
Generation, Transmission and Distribution, IEE Proceedings-
Publisher :
iet
ISSN :
1350-2360
Type :
jour
DOI :
10.1049/ip-gtd:19990410