  • Author

    Gustafsson, M.N. ; Krantz, N.U. ; Daalder, J.E.

  • Author_Institution
    Dept. of Electr. Power Eng., Chalmers Univ. of Technol., Goteborg, Sweden
  • Volume
    144
  • Issue
    3
  • fYear
    1997
  • fDate
    5/1/1997 12:00:00 AM
  • Firstpage
    257
  • Lastpage
    262
  • Abstract
    Voltage stability phenomena using a three-phase power system model are investigated. Measurements show that it is possible to run the system on the lower side of the PV-curve. Stable operation conditions of an induction motor load and a combination of induction motor and resistance load are discussed. The effect of generator current limiters on the system PV-curve is illustrated by measurements. It is shown that the armature current limiter has a more severe effect on voltage stability than does the field current limiter. The load characteristic is important for voltage stability once a current limiter is activated
  • Keywords
    current limiters; load (electric); power system measurement; power system protection; power system stability; armature current limiter; field current limiter; induction motor load; load characteristics; measurements; power system PV-curve; resistance load; three-phase power systems; voltage stability phenomena;