• DocumentCode
    1556197
  • Title

    On-line detection and location of low-level arcing in dry-type transformers

  • Author

    Sidhu, Tarlochan S. ; Sagoo, Gurinder S. ; Sachdev, Mohindar S.

  • Author_Institution
    Power Syst. Res. Group, Saskatchewan Univ., Saskatoon, Sask., Canada
  • Volume
    17
  • Issue
    1
  • fYear
    2002
  • fDate
    1/1/2002 12:00:00 AM
  • Firstpage
    135
  • Lastpage
    141
  • Abstract
    This paper describes the development of a microprocessor based system, based on four different physical phenomena, for reliable and accurate detection and location of arcing in dry-type transformers. The proposed technique was tested for actual arcing, generated on a 15-kVA, 230/115-V Y/Δ transformer enclosed in a 30" × 30" × 21" metallic enclosure. Some results showing the performance of the detection and location system are presented in the paper. The technique can be applied to detect arcing in metal-clad low-voltage/medium voltage switchgear, drives, gas insulated switchgear (GIS), generator bus-ducts, and other metal-clad electrical apparatus against arcing
  • Keywords
    arcs (electric); computerised monitoring; fault location; power transformers; 115 V; 15 kVA; 21 inch; 230 V; 30 inch; dry-type transformers; gas insulated switchgear; generator bus-ducts; low-level arcing; metal-clad LV/MV switchgear; metal-clad electrical apparatus; metallic enclosure; online arcing detection; online arcing location; Acoustic sensors; Acoustic signal detection; Cameras; Gas insulation; Infrared sensors; Power system reliability; Switchgear; Testing; Thermal stresses; Transformers;
  • fLanguage
    English
  • Journal_Title
    Power Delivery, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0885-8977
  • Type

    jour

  • DOI
    10.1109/61.974200
  • Filename
    974200