DocumentCode :
1556245
Title :
Phase-to-ground and phase-to-phase sparkover characteristics of external insulation at the entrance of a UHV substation
Author :
Yamagata, Yoshibumi ; Oe, Akio ; Miyake, Kunihiko ; Aihara, Yoshinori ; Shindo, Takatoshi
Author_Institution :
Tokyo Electr. Power Co. Inc., Japan
Volume :
17
Issue :
1
fYear :
2002
fDate :
1/1/2002 12:00:00 AM
Firstpage :
223
Lastpage :
232
Abstract :
For rational insulation design of a UHV substation, full-scale switching impulse tests of phase-to-ground (shielding ring-to-tower) and phase-to-phase (shielding ring-to-shielding ring) insulating clearance have been carried out in dry and wet conditions. In the tests, shielding rings that will be installed on bushings at actual UHV substations were used. The sparkover voltages depend on not only gap configurations but also the waveform of applied switching impulses; in other words, they show what we refer to as U-characteristics. Critical sparkover voltages are higher than those of rod-rod gaps by 20%-25% in dry conditions and by 7%-10% in wet conditions
Keywords :
air gaps; flashover; shielding; substations; U-characteristics; UHV substation; air gaps; applied switching impulses; bushings; dry conditions; external insulation; full-scale switching impulse tests; gap configurations; insulation design; phase-to-ground insulating clearance; phase-to-phase insulating clearance; rod-rod gaps; shielding ring-to-shielding ring insulating clearance; shielding ring-to-tower insulating clearance; shielding rings; sparkover voltages; surges; wet conditions; Circuit testing; Gas insulation; Geographic Information Systems; Impulse testing; Insulation testing; Insulators; Power transmission lines; Substations; Surges; Voltage;
fLanguage :
English
Journal_Title :
Power Delivery, IEEE Transactions on
Publisher :
ieee
ISSN :
0885-8977
Type :
jour
DOI :
10.1109/61.974211
Filename :
974211
Link To Document :
بازگشت